AAAC Alum Alloy Conductor

Product Group: Power cables , Alt Codes: AAAC , BS No: BS 3242 1970 , Additional Info: Bare O/HD Line, All Voltages
UK Reference: 1 Almond, 2 Cedar, 3 Fir, 4 Hazel, 5 Oak, 6 Ash, 7 Elm, 8 Sycamore, 9 Upas, AAAC
UK CodeConductor materialCore size /mm²No StrandsStrand SizeInsulation materialStrand size
1 AlmondAluminium25.0072.34None
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
82YesYes8.457.02
 
2 CedarAluminium30.007None2.54
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
97YesYes9.957.62
 
3 FirAluminium40.0072.95None
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
131YesYes13.408.85
 
4 HazelAluminium50.0073.30None
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
164YesYes16.809.90
 
5 OakAluminium100.0074.65None
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
325YesYes33.3013.95
 
6 AshAluminium150.00193.48None
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
497YesYes50.6017.40
 
7 ElmAluminium175.00193.76None
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
580YesYes59.1018.80
 
8 SycamoreAluminium250.00373.23None
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
835YesYes85.0022.61
 
9 UpasAluminium300.00373.53None
Additional Info:
Weight(kg/km)StrandedCUT lengthBreaking load (kN)Nom OD MM
997YesYes101.5024.71